zum Seitenanfang

Introduction

Explains the need for data rectification in PVGuard

When developing software monitoring systems, often a major source of complexity comes from having to deal with errors that occur outside the system. PVGuard, is typical here; it receives its data from a multitude of devices spread across a large number of sites. Many of these are located in disparate environments with demanding environmental conditions.

The data received by PVGuard exhibits the usual kinds of problem that can be expected in such situations. Data can be missing, or appear incorrect for reasons including:
  • Malfunctions, either short- or long-term
  • The sudden replacement of defective equipment (either planned or unplanned)
  • Broken communication links, either for accidental or intentional reasons
  • Maintenance activities must be undertaken

So instead of an ideal data stream with regular and reliable data transmission, data outages occur or the data that is received is clearly implausible. Examples of this include, figures for an inverter's output that appear to far exceed its rated figure or, when equipment is replaced, the figures for the cumulative energy production from that device apparently reset to zero.

PVGuard has to deal with all these sorts of error, so as to present the owners and operators with accurate and usable energy data for their plant that they can rely on. The mechanisms employed have been developed by skytron energy over many years of monitoring the actual operation of real systems over time. Its preconfigured plant views show energy figures based this cleaned data.

This document describes the mechanisms employed to check the incoming data, and to rectify the incoming data intelligently, without introducing errors.

Nevertheless, it is important that any such adjustments to the data can be easily identified. Therefore, a necessary prerequisite is that the source data is also saved in its original form. The rectified data is then made available in a "calculated" data channel.

Adjusted energy data channels in PVGuard

Describes the mechanisms used to rectify the energy data in PVGuard

The data rectification process fills the gaps in the original data using interpolation. As part of this, an additional, corrected data channel is added and automatically filled, based on data from the original data channel. The original data channel is always preserved, unchanged, so that it is possible to distinguish between and compare the calculated and the actual measured values​​ at any time.

Data channels containing rectified data can be identified in PVGuard's Plant Explorer (located on the lower left-hand side of the program display) using the symbol f in the icon. An example is shown for a typical inverter in Figure 1. The channels produced as a result of data rectification are usually labelled with the term Adjusted.

Figure 1. PVGuard Plant-Explorer

Energy data rectification

Describes the main functions of the data rectification mechanism in PVGuard.

Identification and removal of implausible discontinuities in the readings

Describes how sudden discontinuities in the received data are treated

Example: The original readings suddenly ​​exhibit a significant "jump" lower. Such behavior might occur after an inverter has been replaced. The energy readings ​​of the new inverter do not correspond to the last reported values ​of the old inverter.

The energy data correction process detects this sudden decrease in reading and, recognising it as needing rectification, adds the detected difference to it and to all subsequent data values​​. In the case of a positive jump in the reading, its plausibility is checked against a predetermined maximum possible power value (e.g. installed peak power, rated power or maximum expected radiation power).

Figure 1. Rectifying a data value discontinuity

Filling gaps in the data (weighted interpolation)

Describes how gaps in the data (i.e. missing data points) are treated

Example: A break in the data link interferes with the continuous record of the measurements.

The data cleaning process attempts to fill in the gaps in the data in such a way that the data can still be used for analysis.

Figure 1. Rectification using interpolation
Note: The aim of the rectification [cleaning] process is to produce a realistic distribution of the difference in energy between the start and end points of a gap in the data. The actual measured values are retained for the start and end points.
To make the distribution of the missing data ​​as realistic as possible, three methods are available for interpolating the data:
  1. Smart interpolation using a reference data channel
  2. Smart interpolation using the solar elevation
  3. Linear interpolation for short gaps
For clarity, in the following diagrams showing the different methods, the energy yield has not been used, but rather the corresponding power output. This is produced by applying the PVGuard Delta aggregate to the corresponding energy data channel, to produce a curve that corresponds to the power output. The difference is shown in Figure 2.
Figure 2. Energy data channels and their Delta aggregate. In the diagram, the total energy produced is shown in red (right axis); the green line (left axis ) shows the change (Delta) in the total energy, which corresponds to the power.

Smart interpolation using a reference data channel

Describes how data is interpolated when a reference channel is available

In this method a reference data channel (usually that of a radiation sensor) is shifted and enlarged/compressed in such a way that its starting and ending values ​​ correspond to the original data readings. This method always produces the best result and is used when a reference data channel is continuously available.

Figure 1. Interpolation using a reference energy data channel

The image below shows the result of simulating a data outage. By this means, the result of the interpolation process has been compared to the actual energy production.

Figure 2. Interpolation compared with actual energy production. The red line shows the actual data and the interpolation is shown in green. The grey, dashed line shows the period of the simulated data outage.

Smart interpolation using the solar elevation

Describes how data is interpolated using the solar elevation

If no reference data channel is available, the solar elevation is used for the interpolation. The energy production is assumed to increase proportionally to the height of the sun above a defined threshold elevation.

Figure 1. Interpolation based on the solar elevation

The image below shows the result of simulating a data outage. By this means, the result of the interpolation process has been compared to the actual energy production.

Figure 2. Interpolation compared with actual energy production. The red line shows the actual data and the interpolation is shown in green. The grey, dashed line shows the period of the simulated data outage.

Linear interpolation for short gaps

Describes how linear interpolation is used to fill short gaps in the data

Linear interpolation is used for very short gaps, as well as to interpolate between two identical or only slightly different readings.

Figure 1. Linear Interpolation

Numerical integration to derive energy data from power

Describes how energy data is derived from power readings by a numerical integration process

The last form of energy channel cleaning is used in the case of devices that instead of an energy data channel, only provide power output readings. This is the case with some models of inverter. The energy data channel must be calculated by summing the power data. Should there be a gap in the data, the last available reading is assumed to apply for a user-definable time period. The power readings are then subjected to a plausibility check. This process is shown in Figure 1.

Figure 1. Conversion of a power to energy data

Numerical integration to derive energy data from power

Describes how energy data is derived from power readings by a numerical integration process

The last form of energy channel cleaning is used in the case of devices that instead of an energy data channel, only provide power output readings. This is the case with some models of inverter. The energy data channel must be calculated by summing the power data. Should there be a gap in the data, the last available reading is assumed to apply for a user-definable time period. The power readings are then subjected to a plausibility check. This process is shown in Figure 1.

Figure 1. Conversion of a power to energy data
Download

Tutorial

Detailed information about all features of the intelligent SCADA software from skytron energy. Benefits - to keep your investment intact.

PVGuard Platform

Downloads

You can find our system documentation and software - always up-to-date and available in a range of different languages.